title: Troubleshooting OPC-UA connections
slug: how-tos/Rou3-troubleshooting-opc-ua-connections
docTags: UDglSYuzCeqYsFuKMx-fS
createdAt: 2025-09-01T12:17:30.147Z
---

## Common connection issues

| Error                                            | What it Means                                     | How to Fix                                                                                                             |
| ------------------------------------------------ | ------------------------------------------------- | ---------------------------------------------------------------------------------------------------------------------- |
| TCP connection timeout or TCP connection refused | Network/firewall issue                            | Check network path and firewall.<br />Windows: `test-netconnection <ip> -port <port>`<br />Linux: `telnet <ip> <port>` |
| TCP connection refused                           | OPC-UA server not listening on this address/port  | Verify the address and port in the OPC-UA server settings and/or check the logs of the OPC-UA server                   |
| StatusBadTCPEndpointURLInvalid (0x80830000)      | Wrong endpoint address                            | Check and correct the endpoint in server vs. client                                                                    |
| Failed to find suitable endpoint                 | Security settings mismatch                        | Adjust SecurityMode/Policy in client or server                                                                         |
| StatusBadIdentityTokenInvalid (0x80200000)       | Wrong username/password or credentials not needed | Enter correct credentials, or remove them if not needed                                                                |
| EOF / BadSecurityChecksFailed (0x80130000)       | Certificate not accepted yet                      | Accept the client certificate on the server                                                                            |
| Unstable (collector health)                      | Multiple consecutive read requests failed         | Check the specific issue in the collector logs                                                                         |

## Other connection issues

- **Time difference:** If clocks are too much out of sync (hours, not seconds), security tokens may expire too soon. Sync all clocks with NTP.

## Common OPC-UA status codes

When collecting data from an OPC-UA server, each value comes with a status code that tells you if the data is reliable (Good) or if there is a problem with it. Here are some common status codes and what they mean.

| Status Code                                                | Meaning                                                          | What to Do                                                                                   |
| ---------------------------------------------------------- | ---------------------------------------------------------------- | -------------------------------------------------------------------------------------------- |
| Bad (0x80000000)                                           | Unspecified issue with the data                                  | Check the data at the source                                                                 |
| BadNodeIDUnknown (0x80340000)                              | The NodeID is unknown to the server                              | Browse the server to find the correct NodeID                                                 |
| BadNodeIDUnknown (0x80340000), but only for monitored data | The namespace is incorrect                                       | Try another namespace, e.g. ns=2 instead of ns=3 or vice versa                               |
| BadTooManyOperations (0x80100000)                          | Too many operations in one request                               | Lower the `MaxNodesPerRegister` and/or `MaxNodesPerRead` setting                             |
| BadTooManyMonitoredItems (0x80DB0000)                      | Too many monitored items for the server                          | Adjust server limits or split over multiple collectors<br />Sometimes: clean up old sessions |
| GoodOverload (0x002F0000)                                  | Server can't keep up with requested rate                         | Lower the update rate or increase server resources                                           |
| BadTimeout (0x800A0000)                                    | Server couldn't provide a value in time                          | Check network, device status and server resources                                            |
| BadNothingToDo (0x800F0000)                                | Client requested an action that does not change anything (no-op) | Nothing                                                                                      |
| BadOutOfMemory (0x80030000)                                | Server cannot complete the request due to RAM limitations        | Lower the update rate or increase server resources                                           |

For a full list of OPC-UA status codes, see the [official list](https://github.com/OPCFoundation/UA-Nodeset/blob/latest/Schema/StatusCode.csv).

## Factry status codes

Factry has added a few of our own status codes to highlight specific issues.

| Status Code                                                          | Meaning                                                     | What to Do                                                       |
| -------------------------------------------------------------------- | ----------------------------------------------------------- | ---------------------------------------------------------------- |
| BadInvalidNodeID                                                     | The NodeID in your settings contains syntax errors          | Enter a valid NodeID                                             |
| BadFactryOPCUARegisterNodesFailed                                    | Collector failed to register nodes (often too many at once) | Lower the `MaxNodesPerRegister` and/or `MaxNodesPerRead` setting |
| BadFactryMonitorError / Error from subscription notification channel | Collector failed to monitor nodes (often too many at once)  | Lower the `MaxNodesPerMonitor` setting                           |
| BadNoValueAtArrayIndex                                               | Array index out of bounds or missing value                  | Check the `ArrayIndex` setting                                   |
| BadFactryOPCUATooManyOpenReadRequests                                | New read requests open faster than they are processed       | Check network, device status and server resources                |
| UnknownStatusCode\_0xXXX                                             | Status code outside OPC-UA spec                             | Check server docs                                                |
| BadFactryInvalidDataForDatatype                                      | Data can't be parsed to the requested type                  | Check the `Datatype` setting                                     |

## Other data collection issues

### Value for monitored measurement after reconnect

Whether monitored measurements receive a value after a reconnect depends on the implementation of the OPC-UA server. There are 3 options:

- The server does not send a value
- The server sends the latest value with its original timestamp
- The server sends the latest value with the current timestamp

Depending on the behavior, a monitored measurement can keep a bad quality for a while after reconnect. Since the quality is only updated when points come in, the bad quality will remain until new Good data arrives.

### x509: invalid basic constraints

The log `Error attempting to reconnect to OPC-UA server: x509: invalid basic constraints`indicates that the OPC-UA server certificate is not valid.
Update the collector to [v2.0.3](https://docs.factry.io/changelog/opc-ua-collector#v203) or higher or contact your OPC-UA server vendor to update the server certificate to a valid one if the issue persists.

### Kepware

For issues specific to Kepware, have a look at [Kepware troubleshooting](docId\:B5Nu0JEkqROHMcG7xfU3C).

### Low-level debugging

If necessary, low-level OPC-UA logging can be enabled to debug connection issues. To do so, set the [LogLevel](docId\:im-7Bhp1Lmte9WPvndn_Y) to 'trace'.
If that option is not available, [update the collector](docId\:g3adOd9UPOm4AlSlqULWR) to [v2.1.0](https://docs.factry.io/changelog/opc-ua-collector#v210) or higher or follow the steps described [here](docId\:HCpRRBDF014CY4o9r3w1i).