title: Configuring an MQTT (JSON) collector
slug: how-tos/bg5N-c
docTags: NdAmj9E8yTRkwQ9gl8SF9,db2K1XGTHf4IBn7zhpSb4
createdAt: 2025-09-09T10:01:08.334Z
---

The MQTT collector in Factry Historian allows you to subscribe to MQTT broker topics and historize incoming data. Once configured, the data becomes available for trending, reporting, and further analysis.

## Prerequisites

- Permissions in Factry Historian to *manage* collectors. See [Privileges](docId\:K2NnYEcUxqQsiuCLmpfKH).
- An installed MQTT collector. If you have not done so already, first [install a collector](docId\:Iv4_SD56TdxcqKRKCj4kv).
- A running MQTT broker that your collector can connect to. If you are running into issues or setting this up for the first time, follow our guide to [test an MQTT connection](docId:9wwoFhAT2N58ssdMPV2Rv).
  - **Optional** but strongly recommended: TLS certificates for secure broker communication.
- A configured [time-series database](docId\:F8UdoT0apxmjws-t-GcPV) to write the collected data to.

## Configure the collector

After installing the collector, you should see that the collector is in an <font color="#46abdd">**initial state**</font> and is actively running. This means that the collector has established a connection to Factry Historian and is awaiting further configuration.

![](https://api.archbee.com/api/optimize/SMPo4IS9FkillUAMsur2c/jsfNA9i2exlB1XSw8esMb-20250924-134518.png)

To configure the collector, select it from the Collectors overview in Factry Historian and click the **Edit** button. Configure the following fields:

### MqttURL

This is the **connection URL of the MQTT broker** the collector should connect to. The URL must point to a reachable broker instance.

For example:

:::BlockQuote
tcp\://broker.example.com:1883   # Without TLS
ssl://broker.example.com:8883   # With TLS (recommended for production)
:::

### ClientCertificate

Determines whether the collector uses a **client certificate** to authenticate with the broker.

- **false** (default)
  &#x20;No client certificate is used.
- **true**
  &#x20;The collector will attempt to use a configured certificate and private key to authenticate.

Use this option only if your broker requires client-side certificates.

### Username and Password

If your MQTT broker requires **user authentication**, enter a valid username and password here.

- Leave empty if your broker allows anonymous connections (only suitable for test environments).
- In production, authentication is strongly recommended.

### Topics

A **comma-separated list of topics** the collector should subscribe to.
Wildcards are supported:

- \+ matches exactly one level.
- \# matches multiple levels and must be the last character in the topic.

For example:

:::BlockQuote
factory/+/temperature
factory/#
:::

This field is required.

### QoS

The **Quality of Service (QoS)** level with which the collector subscribes to topics.

- **0 - At most once**
  &#x20;Messages may be lost, no retries.
- **1 - At least once (default)**
  &#x20;Messages are retried until acknowledged. May result in duplicates.
- **2 - Exactly once**
  &#x20;Highest reliability, no duplicates. More overhead.

For most industrial data, QoS 1 offers the best balance between reliability and performance.

### PersistentSession

Controls whether the MQTT session is persistent.

- **true (default)**
  The broker stores session information and caches messages while the collector is offline, delivering them once it reconnects.
- **false**
  No session state is stored. Messages published while the collector is offline will be lost.

Keep persistent sessions enabled in production to avoid losing data during temporary outages.

### Time & timestamps

The **default layout of the timestamp** for measurements.
If empty, **RFC3339** will be used. If timestamps are in UNIX format, use one of:

:::BlockQuote
UNIX | UNIXMILLIS | UNIXMICROS | UNIXNANOS
:::

**More info:** [https://pkg.go.dev/time#Layout](https://pkg.go.dev/time#Layout)

**Examples**

:::BlockQuote
RFC3339          2025-09-18T09:45:00Z
UNIX             1695020700
UNIXMILLIS       1695020700000
UNIXMICROS       1695020700000000
UNIXNANOS        1695020700000000000
:::

:::hint{type="info"}
You can **override** the collector’s default per measurement by setting **TimestampLayout** together with **TimestampPath** on that measurement.
:::

In RFC3339, a timestamp must include either Z (UTC) or an explicit offset (e.g., +02:00) to avoid ambiguity.

## Adding measurements

Follow the guide on [Adding measurements to an MQTT (JSON) collector](docId\:ZHUYjz8FTlrp-T3TsBuL1)

## Best practices

- Use TLS to secure connections in production.
- Prefer QoS 1 for most industrial data, unless message duplication is unacceptable.
- Keep topics structured and predictable. Avoid deep hierarchies with wildcards everywhere.
- Validate JSONPath expressions before deploying, using tools like jsonpath.com.
- Sync clocks on broker, collector, and clients with NTP to avoid timestamp issues.

## Limits

- A single collector can handle thousands of topics and high-frequency messages.
- Limitations usually arise at the broker level (throughput, connections) or in the JSON parsing overhead.
- If performance becomes an issue, consider splitting topics across multiple collectors.

## Troubleshooting MQTT collector

Typical issues:

- Collector shows "Disconnected" → Check broker address, credentials, and TLS certificates.
- Messages received but no measurements → Verify JSONPath expressions in measurement configuration.
- Timestamps not parsed → Ensure correct TimestampLayout is set.