General settings
Available at Configuration > General, are the following fieldsets:
API
The information configured here will be incorporated in the Token when configuring collectors. If any of these are changed, existing collectors will need to have their token updated. These settings are only used by the collectors, the historian itself will use the values configured in the configuration file.
GRPC port
Description: The gRPC port is the TCP port used by the historian server to communicate with factry collectors. This should reflect the value entered for GRPC_PORT variable in the configuration file /etc/systemd/system/environments/factry-historian-server. Default: 8001
REST port
Description: The REST port is the TCP port on which the historian server REST API and management interface is exposed. This should reflect the value entered for PORT variable in the configuration file /etc/systemd/system/environments/factry-historian-server, unless you are using a reverse proxy in front of Factry Historian, in which case this should reflect the port that is exposed by your reverse proxy. Default: 8000
URL
Description: This value is used by the factry collectors to derive the ip address to communicate with the historian server API. A valid and reachable URL is required here for collector communication to work. Default: http://127.0.0.1
Authentication
Session inactive duration
Description: The time after which an inactive login session expires. This setting accepts duration string literals, eg 1w2d7h15m (1 week 2 days 7 hours and 15 minutes). Default: 7d
Base URL
Description: The URL on which the Factry Historian frontend is available. This settings is important in order for GoogleGoogle and/or MicrosoftMicrosoft authentication providers to work.
Statistics
Allow historian to send statistics
Description: This setting will enable the historian server to send statistics to our Portal. If this setting is disabled, automatic monitoring and alerting will not work. Default: true
Collector Updates
Allow historian to check for updates
Description: If enabled the historian server will check for updates to the collectors. Default: true
Update check interval
Description: The interval at which the historian server will check for updates to the collectors. This setting accepts duration string literals, e.g., 1w2d7h15m (1 week 2 days 7 hours and 15 minutes). Default: 1h
General Logs
Minimum Free Space (MB)
Description: The minimum free disk space in MB required to log to disk. If the free disk space falls below this threshold, logs will be dropped. Default: 2048
Limit logs
Description: If enabled, logs sent to the internal database will be rate limited. Default: true
Log Rate
Description: The maximum allowed number of logs per second. If this threshold is exceeded, logs will be dropped. Default: 50
Log Burst
Description: The maximum number of log lines that can be sent in a single burst. This is used to allow a temporary spike of logs. Default: 500
Limit By Level
Description: If enabled, the log rate limit will be applied to each log level separately. If disabled, the limit will be applied to all logs regardless of their level. Default: true
Audit Logs
Duration to keep audit logs
Description: The duration to keep the audit logs. This setting accepts duration string literals, e.g., 1w2d7h15m (1 week 2 days 7 hours and 15 minutes). Set to 0d to keep indefinitely. Default: 0d
Time-series Cache
Enabled
Description: If enabled, the historian will cache time series data in memory. This will speed up queries but will consume more memory. Default: true
Global cache size
Description: How many points to keep at most in the global cache. Measurements that produce more data will consume more memory, up to the measurement cache size limit. Default: 4194304
Measurement cache size
Description: How many points to keep at most in the cache per measurement. This cannot exceed the global cache size. Default: 4096