Troubleshooting
Most problems show up in the Ignition Gateway logs under Diagnostics > Logs. Filter on FactryHistorian. Enabling Debug logging on the profile adds per-call detail.
Historian profile does not show as Running
Usually an invalid or expired collector token, a blocked port between the gateway and Factry Historian, or a TLS trust failure. The log entry names the cause.
TLS handshake failures
Find out whether the Historian presents a public, internal or self-signed certificate. For an internal or enterprise CA, paste the CA into Custom CA certificate (PEM) on the profile rather than enabling Skip TLS verification. The certificate's host name must match the host carried in the collector token.
The collector shows as inactive in Factry
The module registers and reports health on startup and periodically. An inactive collector means the gateway cannot reach Factry Historian, or the historian profile is not running.
Tags not appearing in Factry
Confirm the tag's Storage Provider is set to the Factry profile in Ignition Designer, that History Enabled is true, that the tag's value actually changes, and that the module status is Running.
Data is stored in Factry but missing from the Ignition tag browser
Ignition refreshes its measurement cache every 30 seconds, so a newly created measurement can take that long to appear.
A measurement has no description or unit of measure in Factry
The tag's description and engineering range are only sent when Include Metadata is true on the tag, and they are only applied when the measurement is created. A tag historized before that setting was turned on keeps an empty description and unit until its measurement is recreated. Filling them in on the measurement in Factry works too.
The tag browser shows a flat list instead of a folder tree
Set Tag path delimiter to / on the historian profile.
Pending count grows and never drains
The module retests connectivity every 30 seconds. After the Historian is reachable again, forwarding resumes within that window. See Store and forward.
Quarantined count grows
Usually a data type mismatch between the Ignition tag and the Factry measurement, or an expired token. The log entry states the reason.
A measurement deleted in Factry does not normally quarantine anything: the module recreates it on the next write. It does quarantine when the recreated measurement never reaches Active, so check that the collector has a default time series database.
Throughput questions
Enable Debug logging on the profile. The gateway log then shows each store and query call, with the number of points and rows involved.